top of page

The EnergyPro is a major step up from our hugely successful SPC Pro data logger, and is designed for the user who needs to do more than measure and manage their energy and carbon, although of course it can still carry out that role with ease.

 

FEATURES

  • Full 6 channel measurement
  • THD and Harmonics on both current and voltage
  • Auto ranging Flex CTs
  • On-board ‘connection diagram’ display eliminates hook-up errors
  • Huge 1 GB memory

 

DESCRIPTION

The EnergyPro is a major step up from our hugely successful SPC Pro data logger, and is designed for the user who needs to do more than measure and manage their energy and carbon, although of course it can still carry out that role with ease.

In addition to providing full 6 channel current and voltage measurement on 3 phase supplies, the EnergyPro also provides a full THD (total harmonic distortion) and harmonics measurement (to the 16th multiple) capability, as well as on-board calculation of current and voltage imbalance. As you would expect, it’s also highly accurate, and like all Elcomponent data loggers, remarkably easy to use.

It ships with the ‘PowerView’ software package which has been carefully tailored to provide both basic energy management data and potentially complex power quality information in a simple and straightforward manner. THD profiles, harmonic bar charts and waveform presentations, are all available at the click of a mouse, and unlike many 3 phase meter solutions we’ve kept it simple, so you get the information you need, presented in an easily understood chart in seconds.

 

The Energy Pro is ideal where power quality may be an issue, or where measurements need to be made on highly distorted supplies where is will not only provide accurate results, but also provide the harmonics fingerprint and waveform characteristics of both the current and the voltage. It’s designed for professional electricians and engineers who often need to acquire highly detailed levels of information, which is why the data logger ships with a huge 1GB memory card – enough for 7 days logging even at a 1 second storage rate, or well over 2 months at a 10 second interval!

 

PARAMETERS: Amps, Volts, kW, kVA, kWh, PF, THD, Harmonics, Hz

 

SPECIFICATION 
Accuracy:+/- 0.5 of full scale for V&I
Safety:IEC 1010 600V CAT III
Flex CT Rating:20/200/2000

EnergyPro Energy & Power Quality Analyser

£2,095.00Price
  • INPUT CHANNELS: 4 x Voltage via voltage leads n 3 x current via flex type CTs

    RANGES: 1 x Voltage range: 0-600 VAC 45-65 Hz n 3 Current ranges: 2-20A, 20-200A, 200-2000A Fully auto-ranging

    DIMENSIONS: Unit: L=232mm H=110mm W=192mm (Excluding CTs) n Flex CT diameter: 150mm n Flex CT length: 450 mm n Flex CT cable length: 1.8m

    PROTECTION LEVEL: IP55 (lid closed) Excludes power cable connection Case: Peli ABS

    SERVICE CONDITIONS: Operating Temperature: -20 to 60oC n Humidity; Max 80% relative non-condensing

    POWER SUPPLY: Integral from measurement voltage n Internal battery back-up (30 hours run time, fully charged)

    MEASUREMENT: Technique: Digital Sampling n Sample rate: 32 Samples/Cycle (45-65 Hz)

    MEASUREMENT PARAMETERS: Min/Max/Avg trend for Voltage, Current, Power, Power Factor, THD, Frequency, Energy n Waveform Capture and Harmonic Trend to 15th Harmonic on V&I.

    STORAGE: Removable Card 1GB Flash – 65000 Records. n Programmable Storage Rate. n Survey length at 1 minute storage: 420 days

    ACCURACY: Voltage: 0.5% of scale n Current: 0.5% of scale

    STANDARDS: Electrical Safety: o Unit: IEC1010 600V CAT III o Flex CTs: IEC1010 1000V Cat III

bottom of page